This page and the next one describe general requirements for temporary wiring
conditions.
- Feeders
shall originate in an approved distribution center. The conductors shall be run as
multi-conductor cord or cable assemblies, or they may be run as open conductors or
insulators not more than 10 feet apart if they will not be subject to physical damage.
- Branch circuits shall originate in an approved power outlet or panelboard. Conductors
shall be open conductors or multi-conductor cord or cable assemblies. If run as open
conductors, branch circuits shall be fastened at ceiling height every 10 feet. No branch-
circuit conductor may be laid on the floor, and each branch circuit that supplies
receptacles or fixed equipment shall contain a separate equipment
grounding conductor.
- Receptacles used in temporary wiring circuits must provide a connection for an equipment
grounding conductor. Unless the receptacle is supplied by a metallic raceway that provides
a continuous grounding path back to the source, a separate equipment grounding conductor
must be placed in the branch circuit. There must be good electrical connection between the
receptacle grounding terminal and the equipment grounding conductor.
|