SPRAY FINISHING

.

Closed Top, Open Face or Front Spray Operations

For spraying operations conducted within a closed top, open face or front spray booth, Class I or Class II, Division 2 location applies to the space within 3 feet in all directions (#1 in drawing) from the opening other than the open face or front. The Class I or Class II, Division 2 location extends from the open face front of the spray booth in accordance with the designations below.
  • If the ventilation system is not interlocked with the spraying equipment so as to make the spraying equipment inoperable when the ventilation system is not in operation, the space shall extend 10 feet (#2 in drawing) from the open face or front of the spray booth.
  • If the ventilation system is interlocked with the spraying equipment so as to make the spraying equipment inoperable when the ventilation system is not in operation, the space shall extend 5 feet (#2 in drawing) from the open face or front of the spray booth.