. | FLAMMABLE AND COMBUSTIBLE LIQUIDS |
. | |
Container and Portable Tank Storage - Fire Control |
|||
Suitable fire control devices, such as small hoses or portable fire
extinguishers, shall be available at locations where flammable
or combustible
liquids are stored. At least one portable fire extinguisher having a rating of not less than 12-B shall be located:
Portable fire extinguishers must be located a minimum distance away from the storage room because fires involving Class I and Class II flammable liquids are likely to escalate rapidly. If the fire is too close to the storage area, it may be impossible to get to it once the fire has started. |
|||
. |