40 CFR Part 264 -- STANDARDS FOR
OWNERS AND OPERATORS OF HAZARDOUS WASTE TREATMENT, STORAGE, AND DISPOSAL FACILITIES
§264.1032 Standards: Process vents.
(a) The owner or operator of a facility with process vents associated with distillation,
fractionation, thin-film evaporation, solvent extraction, or air or steam stripping
operations managing hazardous wastes with organic concentrations of at least 10 ppmw shall
either:
(1) Reduce total organic emissions from all affected process vents at the facility below
1.4 kg/h (3 lb/h) and 2.8 Mg/yr (3.1 tons/yr), or
(2) Reduce, by use of a control device, total organic emissions from all affected process
vents at the facility by 95 weight percent.
(b) If the owner or operator installs a closed-vent system and control device to comply
with the provisions of paragraph (a) of this section the closed-vent system and control
device must meet the requirements of §264.1033.
(c) Determinations of vent emissions and emission reductions or total organic compound
concentrations achieved by add-on control devices may be based on engineering calculations
or performance tests. If performance tests are used to determine vent emissions, emission
reductions, or total organic compound concentrations achieved by add-on control devices,
the performance tests must conform with the requirements of §264.1034(c).
(d) When an owner or operator and the Regional Administrator do not agree on
determinations of vent emissions and/or emission reductions or total organic compound
concentrations achieved by add-on control devices based on engineering calculations, the
procedures in §264.1034(c) shall be used to resolve the disagreement.
§264.1033 Standards: Closed-vent systems and control devices.
(a)(1) Owners or operators of closed-vent systems and control devices used to comply with
provisions of this part shall comply with the provisions of this section.
(2) The owner or operator of an existing facility who cannot install a closed-vent system
and control device to comply with the provisions of this subpart on the effective date
that the facility becomes subject to the provisions of this subpart must prepare an
implementation schedule that includes dates by which the closed-vent system and control
device will be installed and in operation. The controls must be installed as soon as
possible, but the implementation schedule may allow up to 18 months after the effective
date that the facility becomes subject to this subpart for installation and startup. All
units that begin operation after December 21, 1990, must comply with the rules immediately
(i.e., must have control devices installed and operating on startup of the affected unit);
the 2-year implementation schedule does not apply to these units.
(b) A control device involving vapor recovery (e.g., a condenser or adsorber) shall be
designed and operated to recover the organic vapors vented to it with an efficiency of 95
weight percent or greater unless the total organic emission limits of §264.1032(a)(1) for
all affected process vents can be attained at an efficiency less than 95 weight percent.
(c) An enclosed combustion device (e.g., a vapor incinerator, boiler, or process heater)
shall be designed and operated to reduce the organic emissions vented to it by 95 weight
percent or greater; to achieve a total organic compound concentration of 20 ppmv,
expressed as the sum of the actual compounds, not carbon equivalents, on a dry basis
corrected to 3 percent oxygen; or to provide a minimum residence time of 0.50 seconds at a
minimum temperature of 760 °C. If a boiler or process heater is used as the control
device, then the vent stream shall be introduced into the flame zone of the boiler or
process heater.
(d)(1) A flare shall be designed for and operated with no visible emissions as determined
by the methods specified in paragraph (e)(1) of this section, except for periods not to
exceed a total of 5 minutes during any 2 consecutive hours.
(2) A flare shall be operated with a flame present at all times, as determined by the
methods specified in paragraph (f)(2)(iii) of this section.
(3) A flare shall be used only if the net heating value of the gas being combusted is 11.2
MJ/scm (300 Btu/scf) or greater if the flare is steam-assisted or air-assisted; or if the
net heating value of the gas being combusted is 7.45 MJ/scm (200 Btu/scf) or greater if
the flare is nonassisted. The net heating value of the gas being combusted shall be
determined by the methods specified in paragraph (e)(2) of this section.
(4)(i) A steam-assisted or nonassisted flare shall be designed for and operated with an
exit velocity, as determined by the methods specified in paragraph (e)(3) of this section,
less than 18.3 m/s (60 ft/s), except as provided in paragraphs (d)(4) (ii) and (iii) of
this section.
(ii) A steam-assisted or nonassisted flare designed for and operated with an exit
velocity, as determined by the methods specified in paragraph (e)(3) of this section,
equal to or greater than 18.3 m/s (60 ft/s) but less than 122 m/s (400 ft/s) is allowed if
the net heating value of the gas being combusted is greater than 37.3 MJ/scm (1,000
Btu/scf).
(iii) A steam-assisted or nonassisted flare designed for and operated with an exit
velocity, as determined by the methods specified in paragraph (e)(3) of this section, less
than the velocity, Vmax, as determined by the method specified in paragraph (e)(4) of this
section and less than 122 m/s (400 ft/s) is allowed.
(5) An air-assisted flare shall be designed and operated with an exit velocity less than
the velocity, Vmax, as determined by the method specified in paragraph (e)(5) of this
section.
(6) A flare used to comply with this section shall be steam-assisted, air-assisted, or
nonassisted.
(e)(1) Reference Method 22 in 40 CFR Part 60 shall be used to determine the compliance of
a flare with the visible emission provisions of this subpart. The observation period is 2
hours and shall be used according to Method 22.
(2) The net heating value of the gas being combusted in a flare shall be calculated using
the following equation:
TABLE/GRAPH OMITTED
where:
HT=Net heating value of the sample, MJ/scm; where the net enthalpy per mole of offgas is
based on combustion at 25 °C and 760 mm Hg, but the standard temperature for determining
the volume corresponding to 1 mol is 20 °C;
K=Constant, 1.74 10^7 (1/ppm) (g mol/scm) (MJ/kcal) where standard temperature for (g
mol/scm) is 20 °C;
Ci=Concentration of sample component i in ppm on a wet basis, as measured for organics by
Reference Method 18 in 40 CFR Part 60 and measured for hydrogen and carbon monoxide by
ASTM D 1946-82 (incorporated by reference as specified in §260.11); and
Hi=Net heat of combustion of sample component i, kcal/9 mol at 25 C and 760 mm Hg. The
heats of combustion may be determined using ASTM D 2382-83 (incorporated by reference as
specified in 260.11) if published values are not available or cannot be calculated.
(3) The actual exit velocity of a flare shall be determined by dividing the volumetric
flow rate (in units of standard temperature and pressure), as determined by Reference
Methods 2, 2A, 2C, or 2D in 40 CFR Part 60 as appropriate, by the unobstructed (free)
cross-sectional area of the flare tip.
(4) The maximum allowed velocity in m/s, Vmax, for a flare complying with paragraph
(d)(4)(iii) of this section shall be determined by the following equation:
Log10(Vmax)=(HT+28.8)/31.7
where:
28.8=Constant,
31.7=Constant,
HT=The net heating value as determined in paragraph (e)(2) of this
(5) The maximum allowed velocity in m/s, Vmax, for an air-assisted flare shall be
determined by the following equation:
Vmax=8.706+0.7084 (HT)
where:
8.706=Constant,
0.7084=Constant,
HT=The net heating value as determined in paragraph (e)(2) of this section.
(f) The owner or operator shall monitor and inspect each control device required to comply
with this section to ensure proper operation and maintenance of the control device by
implementing the following requirements:
(1) Install, calibrate, maintain, and operate according to the manufacturer's
specifications a flow indicator that provides a record of vent stream flow from each
affected process vent to the control device at least once every hour. The flow indicator
sensor shall be installed in the vent stream at the nearest feasible point to the control
device inlet but before the point at which the vent streams are combined.
(2) Install, calibrate, maintain, and operate according to the manufacturer's
specifications a device to continuously monitor control device operation as specified
below:
(i) For a thermal vapor incinerator, a temperature monitoring device equipped with a
continuous recorder. The device shall have an accuracy of 1 percent of the temperature
being monitored in C or 0.5 C, whichever is greater. The temperature sensor shall be
installed at a location in the combustion chamber downstream of the combustion zone.
(ii) For a catalytic vapor incinerator, a temperature monitoring device equipped with a
continuous recorder. The device shall be capable of monitoring temperature at two
locations and have an accuracy of 1 percent of the temperature being monitored in C or 0.5
C, whichever is greater. One temperature sensor shall be installed in the vent stream at
the nearest feasible point to the catalyst bed inlet and a second temperature sensor shall
be installed in the vent stream at the nearest feasible point to the catalyst bed outlet.
(iii) For a flare, a heat sensing monitoring device equipped with a continuous recorder
that indicates the continuous ignition of the pilot flame.
(iv) For a boiler or process heater having a design heat input capacity less than 44 MW, a
temperature monitoring device equipped with a continuous recorder. The device shall have
an accuracy of 1 percent of the temperature being monitored in C or 0.5 C, whichever is
greater. The temperature sensor shall be installed at a location in the furnace downstream
of the combustion zone.
(v) For a boiler or process heater having a design heat input capacity greater than or
equal to 44 MW, a monitoring device equipped with a continuous recorder to measure a
parameter(s) that indicates good combustion operating practices are being used.
(vi) For a condenser, either:
(A) A monitoring device equipped with a continuous recorder to measure the concentration
level of the organic compounds in the exhaust vent stream from the condenser, or
(B) A temperature monitoring device equipped with a continuous recorder. The device shall
be capable of monitoring temperature at two locations and have an accuracy of 1 percent of
the temperature being monitored in C or 0.5 C, whichever is greater. One temperature
sensor shall be installed at a location in the exhaust vent stream from the condenser, and
a second temperature sensor shall be installed at a location in the coolant fluid exiting
the condenser.
(vii) For a carbon adsorption system that regenerates the carbon bed directly in the
control device such as a fixed-bed carbon adsorber, either:
(A) A monitoring device equipped with a continuous recorder to measure the concentration
level of the organic compounds in the exhaust vent stream from the carbon bed, or
(B) A monitoring device equipped with a continuous recorder to measure a parameter that
indicates the carbon bed is regenerated on a regular. predetermined time cycle.
(3) Inspect the readings from each monitoring device required by paragraphs (f)(1) and (2)
of this section at least once each operating day to check control device operation and, if
necessary, immediately implement the corrective measures necessary to ensure the control
device operates in compliance with the requirements of this section.
(g) An owner or operator using a carbon adsorption system such as a fixed-bed carbon
adsorber that regenerates the carbon bed directly onsite in the control device shall
replace the existing carbon in the control device with fresh carbon at a regular,
predetermined time interval that is no longer than the carbon service life established as
a requirement of §264.1035(b)(4)(iii)(F).
(h) An owner or operator using a carbon adsorption system such as a carbon canister that
does not regenerate the carbon bed directly onsite in the control device shall replace the
existing carbon in the control device with fresh carbon on a regular basis by using one of
the following procedures:
(1) Monitor the concentration level of the organic compounds in the exhaust vent stream
from the carbon adsorption system on a regular schedule, and replace the existing carbon
with fresh carbon immediately when carbon breakthrough is indicated. The monitoring
frequency shall be daily or at an interval no greater than 20 percent of the time required
to consume the total carbon working capacity established as a requirement of
§264.1035(b)(4)(iii)(G), whichever is longer.
(2) Replace the existing carbon with fresh carbon at a regular, predetermined time
interval that is less than the design carbon replacement interval established as a
requirement of §264.1035(b)(4)(iii)(G).
(i) An alternative operational or process parameter may be monitored if it can be
demonstrated that another parameter will ensure that the control device is operated in
conformance with these standards and the control device's design specifications.
(j) An owner or operator of an affected facility seeking to comply with the provisions of
this part by using a control device other than a thermal vapor incinerator, catalytic
vapor incinerator, flare, boiler, process heater, condenser, or carbon adsorption system
is required to develop documentation including sufficient information to describe the
control device operation and identify the process parameter or parameters that indicate
proper operation and maintenance of the control device.
(k)(1) Closed-vent systems shall be designed for and operated with no detectable
emissions, as indicated by an instrument reading of less than 500 ppm above background and
by visual inspections, as determined by the methods specified as §264.1034(b).
(2) Closed-vent systems shall be monitored to determine compliance with this section
during the initial leak detection monitoring, which shall be conducted by the date that
the facility becomes subject to the provisions of this section, annually, and at other
times as requested by the Regional Administrator.
(3) Detectable emissions, as indicated by an instrument reading greater than 500 ppm and
visual inspections, shall be controlled as soon as practicable, but not later than 15
calendar days after the emission is detected.
(4) A first attempt at repair shall be made no later than 5 calendar days after the
emission is detected.
(l) Closed-vent systems and control devices used to comply with provisions of this subpart
shall be operated at all times when emissions may be vented to them.
(55 FR 25494, June 21, 1990, as amended at 56 FR 19290, Apr. 26, 1991)
§264.1034 Test methods and procedures.
(a) Each owner or operator subject to the provisions of this subpart shall comply with the
test methods and procedures requirements provided in this section.
(b) When a closed-vent system is tested for compliance with no detectable emissions, as
required in §264.1033(k), the test shall comply with the following requirements:
(1) Monitoring shall comply with Reference Method 21 in 40 CFR Part 60.
(2) The detection instrument shall meet the performance criteria of Reference Method 21.
(3) The instrument shall be calibrated before use on each day of its use by the procedures
specified in Reference Method 21.
(4) Calibration gases shall be:
(i) Zero air (less than 10 ppm of hydrocarbon in air).
(ii) A mixture of methane or n-hexane and air at a concentration of approximately, but
less than, 10,000 ppm methane or n-hexane.
(5) The background level shall be determined as set forth in Reference Method 21.
(6) The instrument probe shall be traversed around all potential leak interfaces as close
to the interface as possible as described in Reference Method 21.
(7) The arithmetic difference between the maximum concentration indicated by the
instrument and the background level is compared with 500 ppm for determining compliance.
(c) Performance tests to determine compliance with §264.1032(a) and with the total
organic compound concentration limit of §264.1033(c) shall comply with the following:
(1) Performance tests to determine total organic compound concentrations and mass flow
rates entering and exiting control devices shall be conducted and data reduced in
accordance with the following reference methods and calculation procedures:
(i) Method 2 in 40 CFR Part 60 for velocity and volumetric flow rate.
(ii) Method 18 in 40 CFR Part 60 for organic content.
(iii) Each performance test shall consist of three separate runs; each run conducted for
at least 1 hour under the conditions that exist when the hazardous waste management unit
is operating at the highest load or capacity level reasonably expected to occur. For the
purpose of determining total organic compound concentrations and mass flow rates, the
average of results of all runs shall apply. The average shall be computed on a
time-weighted basis.
(iv) Total organic mass flow rates shall be determined by the following equation:
TABLE/GRAPH OMITTED
where:
Eh=Total organic mass flow rate, kg/h;
Qsd=Volumetric flow rate of gases entering or exiting control device, as determined by
Method 2, dscm/h;
n=Number of organic compounds in the vent gas;
Ci=Organic concentration in ppm, dry basis, of compound i in the vent gas, as determined
by Method 18;
MWi=Molecular weight of organic compound i in the vent gas, kg/kg-mol;
0.0416=Conversion factor for molar volume, kg-mol/m3 (@ 293 K and 760 mm Hg);
10^6=Conversion from ppm, ppm^1.
(v) The annual total organic emission rate shall be determined by the following equation:
EA=(Eh)(H)
where:
EA=Total organic mass emission rate, kg/y;
Eh=Total organic mass flow rate for the process vent, kg/h;
H=Total annual hours of operations for the affected unit, h.
(vi) Total organic emissions from all affected process vents at the facility shall be
determined by summing the hourly total organic mass emission rates (Eh as determined in
paragraph (c)(1)(iv) of this section) and by summing the annual total organic mass
emission rates (EA, as determined in paragraph (c)(1)(v) of this section) for all affected
process vents at the facility.
(2) The owner or operator shall record such process information as may be necessary to
determine the conditions of the performance tests. Operations during periods of startup,
shutdown, and malfunction shall not constitute representative conditions for the purpose
of a performance test.
(3) The owner or operator of an affected facility shall provide, or cause to be provided,
performance testing facilities as follows:
(i) Sampling ports adequate for the test methods specified in paragraph (c)(1) of this
section.
(ii) Safe sampling platform(s).
(iii) Safe access to sampling platform(s).
(iv) Utilities for sampling and testing equipment.
(4) For the purpose of making compliance determinations, the time-weighted average of the
results of the three runs shall apply. In the event that a sample is accidentally lost or
conditions occur in which one of the three runs must be discontinued because of forced
shutdown, failure of an irreplaceable portion of the sample train, extreme meteorological
conditions, or other circumstances beyond the owner or operator's control, compliance may,
upon the Regional Administrator's approval, be determined using the average of the results
of the two other runs.
(d) To show that a process vent associated with a hazardous waste distillation,
fractionation, thin-film evaporation, solvent extraction, or air or steam stripping
operation is not subject to the requirements of this subpart, the owner or operator must
make an initial determination that the time-weighted, annual average total organic
concentration of the waste managed by the waste management unit is less than 10 ppmw using
one of the following two methods:
(1) Direct measurement of the organic concentration of the waste using the following
procedures:
(i) The owner or operator must take a minimum of four grab samples of waste for each waste
stream managed in the affected unit under process conditions expected to cause the maximum
waste organic concentration.
(ii) For waste generated onsite, the grab samples must be collected at a point before the
waste is exposed to the atmosphere such as in an enclosed pipe or other closed system that
is used to transfer the waste after generation to the first affected distillation,
fractionation, thin-film evaporation, solvent extraction, or air or steam stripping
operation. For waste generated offsite, the grab samples must be collected at the inlet to
the first waste management unit that receives the waste provided the waste has been
transferred to the facility in a closed system such as a tank truck and the waste is not
diluted or mixed with other waste.
(iii) Each sample shall be analyzed and the total organic concentration of the sample
shall be computed using Method 9060 or 8240 of SW-846 (incorporated by reference under
260.11).
(iv) The arithmetic mean of the results of the analyses of the four samples shall apply
for each waste stream managed in the unit in determining the time-weighted, annual average
total organic concentration of the waste. The time-weighted average is to be calculated
using the annual quantity of each waste stream processed and the mean organic
concentration of each waste stream managed in the unit.
(2) Using knowledge of the waste to determine that its total organic concentration is less
than 10 ppmw. Documentation of the waste determination is required. Examples of
documentation that shall be used to support a determination under this provision include
production process information documenting that no organic compounds are used, information
that the waste is generated by a process that is identical to a process at the same or
another facility that has previously been demonstrated by direct measurement to generate a
waste stream having a total organic content less than 10 ppmw, or prior speciation
analysis results on the same waste stream where it can also be documented that no process
changes have occurred since that analysis that could affect the waste total organic
concentration.
(e) The determination that distillation, fractionation, thin-film evaporation, solvent
extraction, or air or steam stripping operations manage hazardous wastes with
time-weighted, annual average total organic concentrations less than 10 ppmw shall be made
as follows:
(1) By the effective date that the facility becomes subject to the provisions of this
subpart or by the date when the waste is first managed in a waste management unit,
whichever is later, and
(2) For continuously generated waste, annually, or
(3) Whenever there is a change in the waste being managed or a change in the process that
generates or treats the waste.
(f) When an owner or operator and the Regional Administrator do not agree on whether a
distillation, fractionation, thin-film evaporation, solvent extraction, or air or steam
stripping operation manages a hazardous waste with organic concentrations of at least 10
ppmw based on knowledge of the waste, the procedures in Method 8240 may be used to resolve
the dispute.