ELECTRICAL SAFETY DESIGN

.

Wiring Methods and Components - Motor Protection

Switches are used as disconnecting means for motors. Specific motor disconnection requirements are listed here:
  • A disconnecting means shall be located in sight from the controller (within 50 feet of the controller). However, a single disconnecting means may be located adjacent to a group of coordinated controllers that are mounted adjacent to each other on a multi-motor continuous process machine. The controller disconnecting means for motor branch circuits over 600 volts, nominal may be out of sight of the controller, if the controller is marked with a warning label giving the location and identification of the disconnecting means which is to be locked in the open position
  • The disconnecting means shall disconnect the motor and the controller from all ungrounded supply conductors and shall be so designed that no pole can be operated independently
  • If a motor and the driven machinery are not in sight from the controller location, the installation shall comply with one of the following conditions:
    • The controller disconnecting means shall be capable of being locked in the open position
    • A manually operable switch that will disconnect the motor from its supply source shall be placed in sight from the motor location.