WELDING, CUTTING, AND BRAZING

.

Oxygen Cylinders

Oxygen cylinders in storage shall be separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a non-combustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour.

This requirement is intended to reduce the possibility of any fire support when a fire occurs among the fuel gas storage.