. | FLAMMABLE AND COMBUSTIBLE LIQUIDS |
. | |
Industrial Plants - Incidental Flammable or Combustible Liquid Storage or Use |
|||
Incidental flammable
and combustible
liquids shall be stored in covered containers when not in use. When they are used or
handled, leakage or spills shall be disposed of promptly and safely, except when the
liquid is in a closed
container. Flammable or combustible liquids shall be drawn from or transferred into vessels, containers, or portable tanks within a building only in the following manner:
Transfer operations must be provided with adequate ventilation. Sources of ignition are not permitted in areas where flammable vapors may travel. Transferring liquids by means of air pressure in a container or portable tank is prohibited. This may result in overpressure which could exceed what the container or tank could withstand. In addition, a flammable atmosphere could be created within the container or tank that is more sensitive to ignition due to the pressure. |
|||
. |