Storage for Disposal - Facility Requirements

A facility used for the storage of PCBs and PCB items designated for disposal must meet the following requirements:

  • Adequate roof and walls to prevent rain water from reaching the stored PCB items.
  • Impervious floor with continuous curbing at least 6 inches high.
  • Containment must be equivalent to twice the internal volume of the largest PCB article or container, or 25% of the total internal 33 volume of all containers.
  • Located above the 100 year flood plain."

[ 40 CFR §761.65(b) ]

Back